Scope of Work/Overview:
RCMP requests the following work: This is a Non-Tenant direct with a D4 priority and an X1 qualifier: Seed funding - To provide needed improvements to the room in order to bring it up to RCMP DSS standards for a Police Equipment Room. Please provide and install the following: The current wall construction of Room 129 in the Yellowknife Detachment is as follows: slab-to-slab.
1. Walls must meet the secure room specification as outlined in PMM: SR-1 (metal mesh), SR-2 (sheet steel), or SR-3 (minimum two layers of ¾” plywood with staggered seams).”CeilingAfter reviewing photo’s supplied by G Division PTSS, it appears that the ceiling is constructed of cement.
2. Remove drop ceiling with removeable panels as it is not permitted, replace with gypsum wallboard, or leave unfinished.Door, Door Frame, & Hardware
3. Replace current door with a hollow core metal door (HCM) and steel frame with anti-spread bracing installed in area of strike bucket and ensure it will accept a 25mm throw dead bolt. Door and frame to be prepared to receive electric lock.▪ Note 1: Penetrations in the door (i.e. grilles, glazing) are not permitted.▪ Note 2: Doors with frozen lever handsets are not secure until the deadbolt is engaged.
4. Install a heavy-duty door closer without hold functions, threshold and door sweep to enhance the door security by making it more difficult for an intruder to manipulate or bypass the door.Supply and Return Duct Openings
5. Install security grilles on existing supply and return duct openings, with expanded steel mesh 2.68mm to 4.11 mm (0.563” to 1.688”) in accordance with PMM, as these duct openings present as a possible concealment area. Furniture, Fixtures and Equipment
6. Install separate lockable storage cabinets for ammunition and Firearms. (RCMP to provide the Storage Cabinets) As per Storage, Display, Transportation and Handling of Firearms Regulations under the Firearms Act, firearms should be stored unloaded, in a room that has
7.Electrical Wiring and conduit runs as per 2023-07-10 Police Equip Room EACS-IDS Statement of Work.7. Additional 120V 15A electrical outlet on dedicated circuit may be added. (High Priority - To be resent as urgent TRF request)****N.Thibault - Potential for G-DIV PTSS to free issue materials. - Spec on these door materials has been sent as of 2024-06-20